Examples INIT
INITIATE:IMMEDIATE
INIT:CONT 1
INITIATE:CONTINUOUS OFF
Query Syntax (for INIT[:IMM]): None
Query Syntax (for INIT:CONT): INIT:CONT?
Returned Parameters: 0 | 1
Related Commands: ABOR, *RST, TRIG
4.3.9 Calibrate Subsystem
The Calibrate Subsystem calibrates the power supply.
4.3.9.1 CAL:IDN
This command updates the power supply’s identification string for the power supply model. The
CAL:IDN string can have up to 100 characters.
Command Syntax: CALibrate:IDN <string>
Parameters: Company Name, Power Supply Model, S/N (string format)
where: Company Name = "Magna-Power Electronics, Inc.,"
Power Supply Model = PS Type+PSVolts+”-“+PSAmps +”,” (The Power
Supply type can be XR, or XRC)
S/N = “S/N: xxx-yyyy”
Examples: For a XR supply rated at 16VDC and 375 ADC
cal:idn Magna-Power Electronics, Inc., XR16-375, SN: 1162-0361,
F/W:1.0
Query Syntax: CAL:IDN?
Returned Parameters: <string>
Related Commands: *IDN
4.3.9.2 CAL:PASS
This command protects against system calibration corruption and initiates the calibration
sequence.
Command Syntax: CAL:PASS <NR1>